Next
Characteristics
SB-606
SB-608
SB-610
SB-612
Rating operating voltage(VAC)
690
690
690
690
Insulation voltage(VAC)
1000
1000
1000
1000
Number of poles
3P/4P
3P/4P
3P/4P
3P/4P
Frame current(AF)
630
800
1000
1250
Rated current(A)
630
800
1000
1250
Neutral current(A)
630
800
1000
1250
Breaking capacity
S
H
S
H
S
H
S
H
Rated breaking capacity (KA R.M.S sysmmetrical) Rated breaking capacity (O-CO-CO) IEC 947-2 VDE 0660 BS 4752
220/240V
60
75
60
75
60
75
60
75
380/415V
55
70
55
70
55
70
55
70
440/500V
50
65
50
65
50
65
50
65
600/660V
42
55
42
55
42
55
42
55
480V
50
65
50
65
50
65
50
65
600V
42
50
42
50
42
50
42
50
Making capacity(KA.peak)
Below 500V
105
143
105
143
105
143
105
143
600/660V
88.2
105
88.2
105
88.2
105
88.2
105
Short time withstand capacity AC 500V
1Sec
50
65
50
65
50
65
50
65
3Sec
30
30
30
30
Operating time
Total breaking time
40ms
Rated closing time
80ms
Number of operating cycles
With rated current
5,000
5,000
5,000
5,000
Without rated current
10,000
10,000
10,000
5,000
Dimensions W*D*H
Drawnout
3P(4P)
375*462*466(W=581).Auto connect H=482
Fixed
3P(4P)
367*462*347(W=577)
Maximum weighting(kg)
Drawnout
3P(4P)
65(85)
65(85)
65(85)
71(86)
Fixed
3P(4P)
35(48)
35(48)
35(48)
44(54)