Characteristics
|
SB-606
|
SB-608
|
SB-610
|
SB-612
|
||||||
| Rating operating voltage(VAC) |
690
|
690
|
690
|
690
|
||||||
| Insulation voltage(VAC) |
1000
|
1000
|
1000
|
1000
|
||||||
| Number of poles |
3P/4P
|
3P/4P
|
3P/4P
|
3P/4P
|
||||||
| Frame current(AF) |
630
|
800
|
1000
|
1250
|
||||||
| Rated current(A) |
630
|
800
|
1000
|
1250
|
||||||
| Neutral current(A) |
630
|
800
|
1000
|
1250
|
||||||
| Breaking capacity |
S
|
H
|
S
|
H
|
S
|
H
|
S
|
H
|
||
| Rated breaking capacity (KA R.M.S sysmmetrical) Rated breaking capacity (O-CO-CO) | IEC 947-2 VDE 0660 BS 4752 |
220/240V
|
60
|
75
|
60
|
75
|
60
|
75
|
60
|
75
|
|
380/415V
|
55
|
70
|
55
|
70
|
55
|
70
|
55
|
70
|
||
|
440/500V
|
50
|
65
|
50
|
65
|
50
|
65
|
50
|
65
|
||
|
600/660V
|
42
|
55
|
42
|
55
|
42
|
55
|
42
|
55
|
||
|
480V
|
50
|
65
|
50
|
65
|
50
|
65
|
50
|
65
|
||
|
600V
|
42
|
50
|
42
|
50
|
42
|
50
|
42
|
50
|
||
| Making capacity(KA.peak) |
Below 500V
|
105
|
143
|
105
|
143
|
105
|
143
|
105
|
143
|
|
|
600/660V
|
88.2
|
105
|
88.2
|
105
|
88.2
|
105
|
88.2
|
105
|
||
| Short time withstand capacity AC 500V |
1Sec
|
50
|
65
|
50
|
65
|
50
|
65
|
50
|
65
|
|
|
3Sec
|
30
|
30
|
30
|
30
|
||||||
| Operating time |
Total breaking time
|
40ms
|
||||||||
|
Rated closing time
|
80ms
|
|||||||||
| Number of operating cycles |
With rated current
|
5,000
|
5,000
|
5,000
|
5,000
|
|||||
|
Without rated current
|
10,000
|
10,000
|
10,000
|
5,000
|
||||||
| Dimensions W*D*H |
Drawnout
|
3P(4P)
|
375*462*466(W=581).Auto connect H=482
|
|||||||
|
Fixed
|
3P(4P)
|
367*462*347(W=577)
|
||||||||
| Maximum weighting(kg) |
Drawnout
|
3P(4P)
|
65(85)
|
65(85)
|
65(85)
|
71(86)
|
||||
|
Fixed
|
3P(4P)
|
35(48)
|
35(48)
|
35(48)
|
44(54)
|
|||||